SmartD: VFD Leakage Current & Ground Fault Protection – Ensuring Safety & Compliance

SmartD: VFD Leakage Current & Ground Fault Protection: Ensuring Safety & Compliance

March 12, 2025

Why the Smallest Currents Matter: Understanding Leakage Current & Ground Faults in Modern VFDs

Imagine a bustling manufacturing plant where machines produce thousands of components every hour. The electrical cabinets buzz with energy, and a labyrinth of cables branches out to every corner, connecting motors large and small. In one corner stands a shiny new Variable Frequency Drive (VFD) controlling a high-horsepower motor. Nearby, an experienced technician named Alex notices something on his handheld meter: a small current is flowing to the ground.

At first, it might seem like no big deal, just a few milliamps. But is it dangerous? Or completely normal? This is the heart of the story, and it brings up a question that might be obvious to an experienced professional but still makes you think deeply: Why do we place so much emphasis on the small currents? Why do engineers and technicians, meticulously measure, analyze, and sometimes worry about these tiny currents that appear to do no harm? The reason, of course, is because these small currents can be indicators—indicators of normal operation, or signs of a potential problem that could cause serious safety issues.

Welcome to the world of leakage current and ground faults in VFD systems. This article will explore these phenomena with a didactic approach, focusing on why they matter, how they behave, and what sets them apart, especially when looking at clean power VFDs. Whether you’ve spent decades in electrical systems or you’re just stepping into this specialized area, this exploration aims to reinforce the concepts and inspire you to dig deeper into the nuances of these tiny but critically important currents.


Setting the Stage: Leakage Current in VFDs

Leakage current is that “small amount of current that flows through an unintended path to ground/earth.” In the context of a VFD, it typically emerges due to capacitances and inductances within the drive or from the high frequency switching in power electronics. If you’ve ever measured ground current in a VFD system, you’ve probably noticed that it rarely is at zero. Instead, there’s almost always a measurable reading—often in the milliamps range. Why is that?

  • Filters: Most VFDs include internal filters to mitigate electromagnetic interference. These filters, by design, have capacitors from the drive’s internal circuitry to the ground. Even when everything is functioning perfectly, a small current (the filter’s design leakage) flows through these capacitors. It’s not a bug; it’s an inherent part of the filtering solution.
  • Motor Cables & Motor Windings: Next, consider those long cable runs from the drive to the motor. With high-frequency PWM signals, these cables act like capacitors between the conductors and any nearby grounded metal conduit. The rapid switching transients lead to a small “charging current” to the ground, which is often measured on the order of milliamps, but for large motors and very long cables, it can reach tens or even hundreds of milliamps.
  • Semiconductor Switching Devices: Whether you’re using IGBTs or SiC MOSFETs, each transistor has parasitic capacitances that can let a small current pass to ground during switching transitions. Again, not a fault condition—it’s simply physics at work.

The Nature of Leakage Current

Leakage current is usually continuous (or quasi-continuous) in normal operation. The amplitude might fluctuate with load, switching frequency, and cable length, but it doesn’t typically spike into the ampere range under normal circumstances. A typical range might be from a few milliamps up to tens of milliamps. The key is that it is expected. In fact, some standards address this directly. For instance, Standard IEC 61800-5-1 (section 4.3.5.5.2.) stipulates that if a drive’s normal touch current is above 3.5 mA AC or 10 mA DC, you must have a protective measure.


Enter the Ground Fault: A True Fault Condition

Now, let’s talk about ground faults. A ground fault is, by definition, an unintended or accidental path for current to flow to the ground. This typically arises due to insulation failures within motor windings or cables. It might be caused by physical damage, moisture infiltration, chemical contamination, or simple aging of materials. When a ground fault occurs, the current level can skyrocket—from amps to hundreds of amps—depending on the system voltage and the impedance of the fault path.

For example, imagine Alex sees a sudden spike in ground current, jumping from a steady 10 mA to 5 A within milliseconds. That’s a strong sign of a ground fault. Protective devices such as circuit breakers, fuses, or ground-fault protective relays typically detect this surge and trip to isolate the equipment, safeguarding people and property. So while leakage currents are generally mild and continuous, a ground fault is a high-magnitude event that demands immediate attention.

Why is it so critical to detect ground faults quickly? Beyond the obvious safety aspect (risk of shock or electrocution), ground faults can destroy motor windings, damage drive components, and cause extended production downtime. Thus, in a properly designed system, you’ll see clear isolation of these high currents within a fraction of a second.


Why the Confusion?

You might be asking yourself: “If one current is normal and the other is a fault, why do so many technicians confuse the two?” The answer lies in a few factors:

  • Both Flow to Ground: A meter placed on the ground conductor merely sees “some current.” If an engineer is not aware of the typical leakage values of a VFD, they might prematurely label any ground current reading as a “fault.”
  • Protective Device Sensitivity: Many residual-current or ground-fault devices are designed with thresholds that might be too low for typical VFD leakage currents. A sensitive device might trip at, say, 30 mA, which is not uncommon as a normal VFD leakage current. Hence, you get nuisance tripping.
  • High-Frequency Components: Standard measuring devices may interpret the high-frequency leakage from PWM signals as a fault if they’re not designed to filter out these components.
  • Loose Terminology: In everyday conversations, people might casually call anything going to ground ‘leakage,’ without distinguishing between normal and fault conditions.

So, Are They the Same?

Absolutely not. Leakage current is expected and often inherent to the design of VFDs—particularly those using PWM with EMI filters. Ground faults, on the other hand, are unplanned events that signal an electrical breakdown and require immediate action. One is normal, the other is not.


A Look at Clean Power VFDs

As technology evolves, there are now Clean Power VFDs that use multi-level SiC MOSFETs to generate a pure sine wave instead of the typical PWM wave. With fewer high-frequency transitions, the entire leakage current profile changes.

  • Minimal High-Frequency Components: Since the Clean Power VFD outputs a true sine wave rather than a high-frequency PWM waveform, there is minimal capacitive coupling to the ground. This reduces the need for large EMI filters, inherently lowering leakage currents and improving compatibility with ground fault protection devices.
  • Active Front End (AFE): A robust, low-distortion input stage ensures that the line side sees a sinusoidal current draw, reducing the overall ground-referenced noise. This gets rid of many common VFD issues, like high-frequency leakage or harmonic-induced ground currents.
  • Easier Ground Fault Detection: Since normal leakage is minimized, the differentiation between a normal ground current and a genuine ground fault becomes more pronounced. Protective settings can be more sensitive without risking nuisance trips.

Nonetheless, let’s not be fooled into thinking Clean Power VFDs eradicate ground faults altogether. Whenever insulation fails, a ground fault remains a ground fault—no matter how sinusoidal the drive’s output is. The real advantage is the clarity in diagnosing the problem because you have a lower baseline of leakage current to sort through.


Bridging Theory & Practice

Picture Alex, our plant technician, working on a brand-new Clean Power VFD installation. After running the cables, testing insulation resistance, and powering up, the drive shows a stable and low leakage current. Now, if that drive were a standard PWM-based VFD with significant EMI filters, Alex might measure 30–50 mA and question whether it’s normal. With the Clean Power VFD, it’s more straightforward for him to interpret the ground current values.

But does that mean Alex can forget about ground fault protection? Absolutely not. If a day later, the drive logs a sudden spike or meltdown in ground current, that signals a true problem—insulation breakdown, moisture intrusion, or mechanical damage. He’ll rely on the drive’s ground-fault detection to trip safely and log the event.


The “Why” That Guides Us

Why should engineers and technicians care about leakage current and ground faults in VFDs?

  • Safety of Personnel: Even small currents can cause serious shock risks if a path through the body is formed. Ground faults, of course, are far more dangerous in magnitude.
  • Protection of Equipment: Proper classification of ground current prevents nuisance tripping and ensures that real faults are cleared quickly, sparing equipment from catastrophic damage.
  • Regulatory Compliance: Standards like IEC 61800-5-1 define minimum requirements for protective earth connections and permissible leakage current levels. Ignoring these can lead to code violations and legal ramifications.
  • Operational Continuity: Minimizing nuisance trips and quickly resolving actual ground faults keeps production lines running, satisfying operational demands and maintaining profits.

A Final Word on Design & Coordination

The key is understanding the nature of the ground currents and coordinating protection accordingly. If your system regularly sees tens of milliamps due to EMI filters, you may need to adjust your ground-fault protective devices or incorporate advanced filtering methods. If you adopt a clean power VFD, you’ll likely see lower leakage current and thus simpler fault discrimination.

But in all cases, the principles remain the same:

  • Leakage Current: Normal, predictable, usually small.
  • Ground Fault: Abnormal, unintended, potentially large, and requires immediate attention.

By recognizing the distinction and applying the right protective strategies, you ensure a safer, more reliable environment—one where Alex and every other technician can confidently interpret ground current measurements without second-guessing whether a small reading is a sign of imminent danger or just the steady hum of a well-designed VFD system.

Understanding the difference between leakage current and ground faults is key for maintaining a safe and efficient VFD system. If you want to ensure your systems are operating at their best, consider conducting a thorough inspection and implementing the right protective measures. Don’t hesitate to reach out to a professional for in-depth analysis and tailored solutions. Your safety and operational efficiency depend on it.

Source

Related Articles


Changing Scene

  • Hammond Manufacturing Strengthens Western Canada Presence with New Strategic Partnerships

    Hammond Manufacturing Strengthens Western Canada Presence with New Strategic Partnerships

    Hammond Manufacturing Company Limited’s Electrical Enclosures Division has recently announced two significant partnerships to enhance its market presence in Western Canada, effective January 6, 2025, with the addition of Sales Agents, Electra Sales and TMC Sales. These firms were selected based on their excellent, longstanding industry reputation and existing complementary product lines. Both companies bring… Read More…

  • EB Horsman Welcomes David Garrett, New Burnaby Branch Manager

    EB Horsman Welcomes David Garrett, New Burnaby Branch Manager

    EB Horsman is pleased to welcome David Garrett as their new Burnaby Branch Manager. David is a customer-driven leader with over 10 years of experience in the electrical and distribution industries. He firmly believes that putting the customer first is the key to success, and he has built his career around delivering exceptional service, strengthening relationships, and ensuring customers have… Read More…


Sponsored Content
The Easy Way to the Industrial IoT

The way to the Industrial IoT does not have to be complicated. Whether access to valuable data is required or new, data-driven services are to be generated, Weidmuller enables its customers to go from data to value the easy way. Weidmuller’s comprehensive and cutting-edge IIoT portfolio applies to greenfield and brownfield applications. Weidmuller offers components and solutions from data acquisition, data pre-processing, data communication and data analysis.

Visit Weidmuller’s Industrial IoT Portfolio.


ADVANCED Motion Controls Takes Servo Drives to New Heights (and Depths) with FlexPro Extended Environment Product Line

Advanced Motion Controls is proud to announce the addition of six new CANopen servo drives with Extended Environment capabilities to their FlexPro line. These new drives join AMC’s existing EtherCAT Extended Environment FlexPro drives, making the FlexPro line the go-to solution for motion control applications in harsh environments.

Many motion control applications take place in conditions that are less than ideal, such as extreme temperatures, high and low pressures, shocks and vibrations, and contamination. Electronics, including servo drives, can malfunction or sustain permanent damage in these conditions.

Read More


Service Wire Co. Announces New Titles for Key Executives

Bruce Kesler and Mark Gatewood have been given new titles and responsibilities for Service Wire Co.

Bruce Kesler has assumed the role of Senior Director – Business Development. Bruce will be responsible for Service Wire’s largest strategic accounts and our growing Strategic Accounts Team.

Mark Gatewood has been promoted to the role of Vice President – Sales & Marketing. In this role, Gatewood will lead the efforts of Service Wire Company’s entire sales and marketing organization in all market verticals.

Read More


Tri-Mach Announces the Purchase of an Additional 45,000 sq ft. Facility

Tri-Mach Elmira Facility

Recently, Tri-Mach Inc. was thrilled to announce the addition of a new 45,000 sq ft. facility. Located at 285 Union St., Elmira, ON, this facility expands Tri-Mach’s capabilities, allowing them to better serve the growing needs of their customers.

Positioning for growth, this additional facility will allow Tri-Mach to continue taking on large-scale projects, enhance product performance testing, and provide equipment storage for their customers. The building will also be the new home to their Skilled Trades Centre of Excellence.

Read More


JMP Parent Company, CONVERGIX Acquires AGR Automation, Expanding Global Reach

Convergix Automation Solutions has completed the acquisition of AGR Automation (“AGR”), a UK-based provider of custom, high-performance automation design and systems integration primarily to the life sciences industry.

Following Convergix’s acquisitions of JMP Solutions in August 2021 and Classic Design in February 2022, AGR marks the third investment in Crestview’s strategy to build Convergix into a diversified automation solutions provider targeting the global $500+ billion market, with a particular focus on the $70 billion global systems integration and connectivity segments. Financial terms of the transaction were not disclosed.

Read More


Latest Articles

  • SmartD: VFD Leakage Current & Ground Fault Protection – Ensuring Safety & Compliance

    SmartD: VFD Leakage Current & Ground Fault Protection – Ensuring Safety & Compliance

    Imagine a bustling manufacturing plant where machines produce thousands of components every hour. The electrical cabinets buzz with energy, and a labyrinth of cables branches out to every corner, connecting motors large and small. In one corner stands a shiny new Variable Frequency Drive (VFD) controlling a high-horsepower motor. Nearby, an experienced technician named Alex… Read More…

  • Siemens: The Future of Intralogistics – Simatic Robot Pick AI Pro

    Siemens: The Future of Intralogistics – Simatic Robot Pick AI Pro

    Siemens is presenting its new developments in industrial automation and digitalization for the intralogistics industry at this year’s Logimat. Faced with global challenges like labor shortages, growing sustainability requirements, and demographic change, the technology company is introducing innovative automation and digitalization solutions that increase efficiency, adaptability, and sustainability in intralogistics. With Simatic Robot Pick AI… Read More…