SK 3313.610 – Liquid Cooling Unit LCU CW
The LCU CW basically consists of an air/water heat exchanger, fans and the controller. It is used to dissipate heat from network/server enclosures and thus effectively cool the components installed in the enclosure.
Product Description
Article Number
- SK 3313.610.
Version
- Rack cooling, CW.
Benefits
- Efficient cooling of network/server enclosures.
- Space-saving due to installation in the enclosure.
- Control of the server inlet temperature.
- Energy efficient DC fans.
- Optimum adaptability due to dynamic, continuous control of the cold-water volume flow.
- Fan modules can be replaced during operation.
Function Principle
- The Liquid Cooling Unit CW is installed in the network/server enclosure next to the 19″ plane.
- The heated air is drawn in at the rear third of the enclosure, cooled via the heat exchanger and blown out again at the front of the enclosure.
Material
- Carbon steel, spray finished.
Color
- RAL 9005.
Supply Includes
- 1 Liquid Cooling Unit CW.
- 1 support element for LCU CW.
- 3 m fabric hose (for condensate discharge).
- 2 angle hose connector 90°.
- 12 screw M5 x 12 self-tapping/NZ/TX30.
- 1 female connector (7-pole).
- 1 set of assembly, installation and operating instructions.
Options
- Connection of a maximum of 16 CMC III sensors.
Monitoring
- Monitoring of all system-relevant parameters such as server air intake temperature, server waste air temperature, water inlet/return temperature, water flow, cooling output, fan speed, leakage.
- Direct connection of the unit via SNMP over Ethernet integration into RiZone.
Temperature Control
- Control of the server inlet temperature.
Protection Category IP to IEC 60 529
- IP 20.
Duty cycle
- 100 %.
Refrigerant/Cooling Medium
- Cooling Medium: Water.
Suitable For
- Enclosure Type: VX IT 19″ Standard profile rails.
- Width: ≥ 800 mm.
- Height: ≥ 2,000 mm.
- Depth: ≥ 1,000 mm.
- Enclosure Type: VX IT 19″ Standard profile rails.
- Width: ≥ 31.5 ˝
- Height: ≥ 78.7 ˝
- Depth: ≥ 39.4 ˝
Dimensions
- Width: 110 mm.
- Height: 1,866.5 mm.
- Depth: 756 mm.
- Width: 4.33 ˝
- Height: 73.5 ˝
- Depth: 29.8 ˝
Rated Operating Voltage
- 90 – 264 V, 1~, 50 Hz/60 Hz.
Air Throughput (Unimpeded Air Flow)
- 1,500 m³/h.
- (882.9 cfm).
Rated Output
- 0.5 kW.
DC Fan
- Yes.
Fans May Be Exchanged With the System Operational
- Yes.
Water Connections
- G ¾” external thread.
Permissible Operating Pressure (P. Max.)
- 1 MPa.
Operating Temperature Range
- 10 °C…50 °C.
- (50 °F…122 °F).
Operating Temperature Range of Cooling Medium
- 10 °C…30 °C.
- (50 °F…86 °F).
Total Cooling Output
- Useful cooling capacity L24 (Server supply air temperature) W15: 7.9 kW.
- Useful cooling capacity L24 (Server supply air temperature) W18: 6.8 kW.
Packaging Unit
- 1 pc(s).
Net Weight
- 92.5 kg.
Gross Weight
- 102.5 kg.
Customs Tariff Number
- 84186900.
EAN
- 4028177973251.
ETIM 9
- EC000855.
ETIM 8
- EC000855.
Brief Description
- SK Liquid Cooling Unit LCU CW, L24/W15: 26956 BTU/h, WHD: 110×1866.5×756 mm.